Click Image to Enlarge
|
|
|
|
|
3-Phase units also available. See bottom of page for Fuel tank and Automatic Transfer Switch (ATS) options:
SP Series: When normal power fails, SENTRY-PRO automatically starts and supplies emergency voltage to your selected loads through an automatic transfer switch. When normal power returns, the generator automatically shuts down and transfers the load from the generator power, back to normal power. The total operation is automatic, meaning no operator needs to be present.
Maximum KW @ Single Phase : 15 Standby KW @ Single Phase : 14 Standby Amps @ 120 Volt : 116 Standby Amps @ 240 Volt : 58
Engine Specs Type: Lister Engine Induction System: Naturally Aspirated Turbo Charger Engine HP Max Rating : 25 Engine Cubic In. Displ. (Liters): 107 (1.8) Engine Cylanders: 4 Fuel Injection System: Direct with "glo" plugs Engine Lubrication: Full Pressure Oil Lubrication & additional Spin-off replacement oil filter Industrial Muffler: Standard Fuel Use @100% Load (Gal/hr): 1.5 Fuel Use @ 75% Load: 1 Engine Alternator Output: 50 Amps at 12 VDC
Generator Regulation All Models: +/-1% Voltage Regulation Frequency (Speed): All Models +/- 5% frequency regulation w/ electronic governor system Engine Cooling: Liquid cooling w/ pusher fan & 125F radiator Protection Controls: Shutdown For: low oil, high-temp, overspeed, overcrank Sentinel 111: Digital Controller, programmable microprocessor, LCD metering of generatot & engine functions "Kleen Power": All Models: Max of 4% distortion on generated Sine Wave Motor Start :10hp Batteries Requires: 12 VDC, 660 CCA, 55 Amp/hr
Products availiable in 3 enclosure styles (Prices will vary): Super-Silent Standard Enclosure Open Set
Please Note: Advertised pricing is for the "Standard" housing option; call us for "Open-Set" and "Super-Silent" price quotes.
(Diesel Powered) 15KW Standby Generator: SPLD-150 Features:
• CONTROL PANEL: Large and spacious for easier installation connections. Panel door is lockable.
• INTERIOR AIR DUCTS: Clean fresh air is forced into the housing resulting in coolest gen-set.
• MUFFLER: Mufflers are used for additional silencing. Exhaust outlet is directed straight up.
• Rust proofed steel enclosure with weather and sound protection, easy service access thru doors.
• MICROPROCESSOR: This digital controller monitors normal utility power constantly.
|
|
|
|
|
|
|
|
|
|
|
| Displacement/ Type |
107 cu.in (1.8L) |
|
|
|
| Dimension (H x L x W) |
32 X
46 X
32
in
|
|
|
|
|
|
|
|
|
| Not all of our products are listed online, please phone us if you are looking for something in particular. 1-800-541-0616 |
|
GIL-SPLD150
|