|
3-Phase units also available. See bottom of page for Fuel tank and Automatic Transfer Switch (ATS) options:
SP Series: When normal power fails, SENTRY-PRO automatically starts and supplies emergency voltage to your selected loads through an automatic transfer switch. When normal power returns, the generator automatically shuts down and transfers the load from the generator power, back to normal power. The total operation is automatic, meaning no operator needs to be present.
Maximum KW @ Single Phase : 130 Standby KW @ Single Phase : 116 Standby Amps @ 120 Volt : 966 Standby Amps @ 240 Volt : 483
Engine Specs Type: John Deere Engine Induction System: Naturally Aspirated Turbo Charger Engine HP Max Rating : 199 Engine Cubic In. Displ. (Liters): 365 (5.99) Engine Cylanders: 6 Fuel Injection System: Direct- "glo" plugs are optional Engine Lubrication: Full Pressure Oil Lubrication & additional Spin-off replacement oil filter Industrial Muffler: Standard Fuel Use @100% Load (Gal/hr): 8.4 Fuel Use @ 75% Load: 6.3 Engine Alternator Output: 55 Amps for charging max amperage at 12 Volts DC
Generator Regulation All Models: +/-1% Voltage Regulation Frequency (Speed): All Models +/- 5% frequency regulation w/ electronic governor system Engine Cooling: Liquid cooling w/ pusher fan & 125F radiator Protection Controls: Shutdown For: low oil, high-temp, overspeed, overcrank Sentinel 111: Digital Controller, programmable microprocessor, LCD metering of generator & engine functions "Kleen Power": All Models: Max of 4% distortion on generated Sine Wave Motor Start :80hp Batteries Requires: (2)12 VDC, 660 CCA, 55 Amp/hr
Products availiable in 3 enclosure styles (Prices will vary): Super-Silent Standard Enclosure Open Set
Please Note: Advertised pricing is for the "Standard" housing option; call us for "Open-Set" and "Super-Silent" price quotes.
(Diesel Powered) 130KW Standby Generator: SPJD-1250 Features:
• CONTROL PANEL: Large and spacious for easier installation connections. Panel door lockable.
• MICROPROCESSOR: This digital controller monitors normal utility power constantly = always on guard.
• HOUSING: Rust proofed steel enclosure with weather and sound protection, easy service access.
• MUFFLER: Mufflers are used for additional silencing. Exhaust outlet is directed straight up.
• INTERIOR AIR DUCTS: Clean fresh air is forced into the housing = coolest running system.
|
|
|
|
|
|
|
|
|
| Diesel KW/Amps |
116/966-483 |
|
| Displacement/ Type |
365 cu.in./ (5.99L) |
|
|
|
|
|
| Dimension (H x L x W) |
53 X
89 X
44
in
|
|
|
|
|
|
|
|
|
| Not all of our products are listed online, please phone us if you are looking for something in particular. 1-800-541-0616 |
|
GIL-SPJD1250
|